Outdoor Pole-Mounted VCB with Primary and Secondary Deep Fusion

Specially engineered for 12kV distribution network overhead lines, it is built to withstand harsh environments and frequent operations, safeguarding the stable operation of the power grid.

Product Description

The HXV8 pole-mounted circuit breaker is an outdoor switchgear developed and designed by our company according to the market demands of the State Grid (SGCC). It is used for the control and protection of 12kV rated voltage, three-phase AC 50Hz distribution network overhead lines. While meeting conventional user requirements, it is also suitable for locations with frequent operations and relatively harsh environmental conditions.

Product Advantages

Outdoor Pole-Mounted VCB with Primary and Secondary Deep Fusion

HXV8-12
Parameter Name UnitValue or Description
Rated Voltage kV12
Rated Insulation Level1min Power Frequency Withstand Voltage (Phase-to-Phase, Phase-to-Ground (Wet Test)/Across Open Contact)kV42/48
 Lightning Impulse Withstand Voltage (Phase-to-Phase, Phase-to-Ground/Across Open Contact)kV75/85
Rated Frequency Hz50
Rated Current A630
Rated Short-Time Withstand Current kA20
Rated Peak Withstand Current kA50
Rated Short-Circuit Current Duration s4
Rated Short-Circuit Breaking Operations Times30
Rated Short-Circuit Breaking CurrentAC Component RMSkA20
 DC Component Percentage 52%
Rated Operating Sequence  0-0.3s-CO-180s-CO
Rated Short-Circuit Making Current kA50
Rated Out-of-Phase Breaking Current kA5
Rated Phase-Opposition Breaking Current kA17.4
Rated Capacitive Switching Current (Class C2)Rated Cable Charging Breaking Current (RMS)A25
 Rated Main Circuit ResistanceμΩ≤80
Mechanical LifeCircuit BreakerTimes12000
 Secondary Circuit 1min Power Frequency Withstand VoltagekV2
Auxiliary and Control CircuitRated Supply VoltageVDC: 24 or Other
 Rated Supply FrequencyHz50
Partial Discharge Level (1.1Ur) pC≤20
Enclosure Protection Rating of Circuit Breaker  IP67
Current SensorPhase Current (Ratio) 600A/1V
 Zero-Sequence Current (Ratio) 20A/0.2V
 Phase Current (Accuracy Class) Protection 5P10, Metering 0.5S, Three-in-One Compatible
 Zero-Sequence Current (Accuracy Class) <1% (1%~120% In), Protection 10P10
 Load Impedance ≥20kΩ
 Implementation Method Low-Power Electromagnetic Type
 Temperature Range -40℃~70℃
Voltage SensorPhase Voltage (Ratio) (10kV/√3)/(3.25V/√3)
 Zero-Sequence Voltage (Ratio) (10kV/√3)/(6.5V/√3)
 Phase Voltage (Accuracy Class) Class 0.5
 Zero-Sequence Voltage (Accuracy Class) Class 3P
 Load Impedance ≥1MΩ
 Implementation Method Capacitive Voltage Divider
 Temperature Range -40℃~70℃
Energy Harvesting SensorRated Primary Input VoltagekV10kV/√3
 Rated Secondary Output Voltage AC190V
 Single-Side Rated Single-Phase Total Harvesting Power 6
ItemUnitParameter
Contact Gap Smm9 ± 1
Contact Overtravel L1mm3 ± 1
Opening Speed (6 mm after contact separation)m/s1.2 ± 0.2
Closing Speed (6 mm before contact touch)m/s0.8 ± 0.2
Opening Timems20 ~ 60
Closing Timems30 ~ 70
Three-Phase Opening/Closing Non-Simultaneityms≤ 2
Contact Closing Bounce Timems≤ 2