Consult Now

Type I Data Concentrator Unit

DJTD23-HX3200

Dedicated to automated data acquisition and smart meter reading in low-voltage power systems.

Product Description

The DJTD23-HX3200 series data concentrator, hereinafter referred to as the Type I Concentrator, is a new-generation centralized meter reading terminal product characterized by advanced technology, stable performance, reliable operation, and easy maintenance, developed based on a 1GHz frequency, quad-core high-performance core board, and a unified operating system software platform, while integrating GPRS/4G/5G/Ethernet remote communication technologies, PLC/RF/dual-mode heterogeneous local communication technologies, and high-precision energy metering technology under modular and object-oriented design philosophies. It is suitable for various levels of power utilities, public institutions, public buildings, residential communities, commercial complexes, and trading markets where multi-meter centralized collection of power consumption data is required but data density demands are relatively low. This product complies with the 2022 technical specifications of the State Grid Corporation of China (SGCC) and the DL/T 698.45 standard—Electricity Information Acquisition and Management System—Part 4-5: Object-Oriented Interoperability Data Exchange Protocol.

Product Advantages

Type I Data Concentrator Unit

DJTD23-HX3200
Main Technical SpecificationsSpecification Description
Communication SpecificationsQ/GDW 1376.1-2013 "Power User Electricity Information Collection System Communication Protocol: Communication Protocol between Master Station and Collection Terminal"
Q/GDW 11778—2017 "Object-Oriented Electricity Information Data Exchange Protocol"
Rated VoltageThree-phase four-wire: 3×220/380V
Specified operating range: 0.8Un~1.2Un
Extended operating range: 0.7Un~1.3Un
Current Specifications3×1.5(6)A
Accuracy ClassActive Energy: 0.5S
Reactive Energy: Class 2
Voltage and Current Accuracy: Class 0.5
Quiescent PowerActive power consumption ≤15W, apparent power consumption ≤25VA
Voltage input circuit power consumption ≤0.5VA (per phase)
Current input circuit power consumption ≤0.25VA (per phase)
Clock AccuracyDaily error ≤0.5s (at reference temperature 23°C), can run continuously for over 5 years after power failure
Backup Battery Capacity4.8V/750mAh rechargeable battery, ensures terminal continuous operation for more than 10 minutes after power failure
Operating TemperatureNormal long-term operating temperature range: -40°C~70°C
Limit range: -45°C~80°C
Storage and Transport Temperature-40°C~70°C
Storage and Operating Humidity≤95%
ReliabilityMTBF≥7.6×10⁴h
Outline DimensionsWall-mounted: 290mm×180mm×95mm
WeightApprox. 2.5kg