Smart Transformer Area Terminal
STTU12-HX01
The China Southern Power Grid Smart Transformer Area Terminal is an intelligent data collection and control terminal installed in public transformer areas. It features data collection, equipment monitoring, energy metering, power consumption management, and remote operation and maintenance, supporting the development needs of marketing, distribution, and emerging businesses.
Product Description
The China Southern Power Grid Smart Transformer Area Terminal (STTU12-HX01) is a core device for the digital transformation of transformer areas in the new power system. It integrates functions such as electrical quantity monitoring, equipment status sensing, load control, edge computing, and multi-mode communication, complying with China Southern Power Grid’s Q/CSG enterprise standards. The terminal adopts a modular hardware architecture and independently controllable “State Grid Chip,” suitable for outdoor wide temperature environments from -40℃ to +70℃, with an MTBF exceeding 30,000 hours and a service life of more than 10 years. It enables transparent management of the entire “transformer-line-user” data chain in the transformer area, supporting intelligent patrol and maintenance and refined user-side operations.
Product Advantages
Smart Transformer Area Terminal
STTU12-HX01
| Technical Specifications | Specifications/Requirements |
| Accuracy Class | Active Energy 0.5/1.0 Reactive Energy 2.0 |
| Reference Voltage | 3P4W: 3×220V/380V |
| Rated Current | 0.01-0.05(10)A/0.1-0.5(80)A (subject to actual terminal) |
| Rated Frequency | 50Hz |
| Outline Dimensions | 290mm×180mm×103mm |
| Operating Voltage | 0.9Un~1.1Un |
| Limit Voltage Range | 0.7Un~1.3Un |
| Total Consumption | Apparent power ≤25VA Current circuit power (single phase): ≤5W and 8VA Voltage circuit power (single phase): ≤1VA |
| Clock Parameters | ≤0.5 s/d |
| Clock Battery Lifespan | 10 years |
| Continuous Runtime | ≥5 years |
| Data Retention after Power Failure | ≥10 years |
| Operating Temp. Range | 25℃~55℃ |
| Limit Temp. Range | -30℃~75℃ |
| Storage & Operating Humidity | ≤95% |
| Master Station Specifications | Enterprise standard Compatible with China Southern Power Grid Metering Automation Terminal Uplink Communication Specification, DL/T634.5-101, DL/T634.5-104, and MOT protocol |
| Meter Specifications | DL/T 645-1997, DL/T 645-2007 |
| Panel Display | 240*160 dot matrix monochrome LCD, LED backlight |
| Keyboard | 6 keys: Up, Down, Left, Right, Cancel, Confirm |
| Data Transmission | Standard: 4G full-netcom wireless communication module and Ethernet port Optional: 5G module |
| Local Communication Interfaces | 1 USB port 1 routing Ethernet port 1 hardware interface 1 connection port |
| Remote Upgrade | Supports resume from breakpoint Supports remote upgrade via Ethernet, wireless public network, etc. |
| Storage Capacity | ≥8GB |
| Operating Memory | ≥1GB |
| Reliability | MTBF≥7.6×10⁴h |
| Supported Functional Modules | Remote communication module Local communication modules (RS-485, M-Bus, CAN, carrier communication) Communication module Control module Branch monitoring module Analog acquisition module, etc. |