Medium Voltage Switchgear
The 12~40.5kV medium voltage switchgear is an armored metal-enclosed switchgear suitable for three-phase AC 50Hz power systems at corresponding voltage levels, used for power distribution and circuit control and protection. It features safe arc-resistant design, has passed authoritative certifications, and can be equipped with intelligent components.
Product Description
Product Advantages
Compact Structure
Modular design results in compact size, space savings, and easy installation and maintenance.

Easy Maintenance
The modular design facilitates easier maintenance and component replacement, reducing outage time.

High safety
The metal armored structure provides excellent mechanical strength and protection, and the internal compartment design effectively isolates arcs, ensuring operational safety and continuity of power supply.

High Reliability
The five-prevention interlock is complete and reliable, preventing misoperation; internal components are made of high-quality materials and have undergone rigorous testing to ensure long-term stable operation.

Good Scalability
Flexible configuration and expansion can be tailored to meet different application scenarios.

Medium Voltage Switchgear
KYN28-12 | KYN28-24 | KYN61-40.5
KYN28-12
| Parameter | Unit | 7.2kV | 12kV |
| Insulation Voltage | kV | 7.2 | 12 |
| Rated Power-Frequency Withstand Voltage | kV/1min | 30 | 42 |
| Rated Lightning Impulse Withstand Voltage | kV | 60 | 75 |
| Rated Frequency | Hz | 50 | 50 |
| Rated Short-Time Withstand Current | kA/4S | 40 | 40 |
| Rated Peak Withstand Current | kA | 100 | 100 |
| Busbar Rated Current | A | 4000 | 4000 |
| Branch Busbar Rated Current | A | 4000 | 4000 |
| Internal Arc Fault Withstand Current | kA/0.5S | 40 | 40 |
| IP Rating | IP4X | IP4X | |
| IK Rating | IK10 | IK10 | |
| Overall Dimensions (W×D×H, excluding front/rear doors) | mm | 650×(800/1000/1200) | |
| Weight | kg | 800-1800 |
KYN28-24
| Parameter | Unit | Value |
| Rated Voltage | kV | 24 |
| Rated Frequency | Hz | 50 |
| Rated Current | A | 630, 1250 |
| Short-Time Withstand Current (4S) | kA | 20, 25, 31.5 |
| Short-Circuit Breaking Current | kA | 20, 25, 31.5 |
| Short-Circuit Making Current (Peak) | kA | 50, 63, 80 |
| Protection Degree | IP4X, IP2X when isolation compartment and circuit breaker compartment doors are open |
KYN61-40.5
| Parameter | Unit | 40.5kV |
| Insulation Voltage | kV | 40.5 |
| Rated Insulation Voltage | kV | 40.5 |
| Rated Power-Frequency Withstand Voltage | kV/1min | 95 |
| Rated Lightning Impulse Withstand Voltage | kV | 185 |
| Rated Frequency | Hz | 50 |
| Rated Short-Time Withstand Current | kA/4S | 31.5 |
| Rated Peak Withstand Current | kA | 80 |
| Busbar Rated Current | A | 2500 |
| Branch Busbar Rated Current | A | 2500 |
| IP Rating | IP4X | |
| Overall Dimensions (W×D×H, excluding front/rear doors) | mm | 1400 (1680) × 2750 (2800/3050/3200) × 2600 |
| Weight | kg | 1000-2000 |