Low-Voltage Draw-out Switchgear
MNS low-voltage withdrawable switchgear is designed for full-scenario applications in power distribution systems up to 4000A, covering core distribution needs across multiple industries.
Product Description
MNS low-voltage withdrawable switchgear is suitable for power generation and distribution systems with AC frequency of 50-60Hz, rated operating voltage of 400V (690V), and rated current up to 4000A. It is used for power distribution, centralized motor control, and reactive power compensation. It is widely applied in power plants, petroleum, chemical, metallurgy, textile, high-rise buildings, and other locations.
3D 模型加载中...
3D 模型加载失败,请检查 GLB 文件格式、压缩扩展或服务器响应。
Product Advantages
Selectable IP Rating
The standard IP rating is IP40, which can be upgraded to IP54 in special environments to adapt to complex conditions such as humidity and dust.

Excellent Electrical Performance
The main busbar can carry a maximum current of 6300A, with a short-time withstand current of 100kA (1s). The busbar uses double-layer ESLOK coated bolted connections to ensure maintenance-free operation.

Reliable busbar system
The busbar is protected by high-strength flame-retardant plastic functional panels with high insulation strength, providing arc fault resistance for safe and reliable operation and maintenance.

Flexible Design
The C-shaped profile with a 25mm modular design offers strong structural versatility and flexible assembly. Using standard modular design, over 200 components can form different frame structures and drawer units to meet various structural forms, IP ratings, and environmental requirements.

Efficient Space Utilization
Compact design accommodates more functional units in a smaller space, with a single cabinet holding up to 72 drawers, increasing capacity by over 30% compared to traditional cabinets.

Low-Voltage Draw-out Switchgear
MNS
Technical Specifications
| Item | Parameters | ||||
| Rated Voltage | Rated Insulation Voltage | AC 690V | AC 1000V | ||
| Rated Operating Voltage | AC 400V | AC 400V | |||
| Rated Impulse Withstand Voltage | 8kV | 12kV (Incoming/Feeder Cabinet), 8kV (Control Cabinet) | |||
| Rated Current | Main Busbar | Rated Current | 2500A | 4000A | 6300A |
| Rated Peak Withstand Current | 105kA | 176kA | 220kA | ||
| Rated Short-Time Withstand Current | 50kA | 80kA | 100kA | ||
| Control Cabinet Distribution Busbar | Rated Current | 1250A | 1500A | 2000A | |
| Rated Peak Withstand Current | 105kA | 105kA | 176kA | ||
| Rated Short-Time Withstand Current | 50kA | 50kA | 80kA | ||
| Feeder Cabinet Distribution Busbar | Rated Current | / | / | 2000A | |
| Rated Peak Withstand Current | / | / | 176kA | ||
| Rated Short-Time Withstand Current | / | / | 80kA | ||
| Rated Frequency | 50Hz | ||||
| IP Rating | IP42 | IP42 | IP43 |