Cover-Type FTU Feeder Terminal
Product Description
Mainly applied to pole-mounted switches on 10kV distribution lines. The distribution automation feeder terminal is primarily used for monitoring line operation status, switch equipment status, fault detection, and switch control on 10kV lines. It can also utilize centralized, adaptive local, voltage-time, and voltage-current-time feeder automation functions for fault detection, isolation, and restoration of power supply to non-fault areas.
3D 模型加载中...
3D 模型加载失败,请检查 GLB 文件格式、压缩扩展或服务器响应。
Product Advantages
Enclosed standardized structure, compliant with State Grid standards.
Fully modular design with standardized internal wiring harness connections.
Dual-zone redundant backup and self-recovery technology for operating system, critical programs, and parameters. The detection accuracy for single-phase ground faults in distribution networks reaches over 90%.
Diverse Communication Methods: Supports fiber optic Ethernet, 4G/5G wireless; communication can be encrypted via software and hardware, with built-in State Grid professional security chip.
Status sensing technology: temperature detection and control, positioning, etc.
With communication capability, supports "remote maintenance" function
Cover-Type FTU Feeder Terminal
HXD837-F30
Technical Specifications
| Parameter Name | Parameter | Remarks |
| Power Source | DC24V | |
| Communication Power Supply | DC24V/DC48V | |
| Communication Channels | At least 3 communication channels. | |
| Telemetry | Collects 2 line voltages, three-phase protection/measurement current, zero-sequence current, zero-sequence voltage | |
| Output Circuits | 2 remote control open/close circuits | |
| Communication Interfaces | 1 Bluetooth interface; 1 hot-swappable 4G/5G module interface; 2 RS232 communication interfaces; 2 Ethernet communication interfaces; 1 serial maintenance port; | |
| Metering Function | Built-in line loss metering | |
| Protection Functions | Three-stage overcurrent protection, two-stage zero-sequence current protection, short-circuit fault alarm, small current grounding line selection, three-shot auto-reclosing, non-interrupting current blocking, undervoltage alarm, zero-sequence overvoltage alarm, PT disconnection alarm, post-acceleration protection | |
| Time Synchronization | GPS/Beidou time synchronization | |
| Connection Type | Circular aviation connector (6-pin PT, 6-pin anti-open circuit current, 14-pin digital input/output) | Connected to the 26-pin aviation connector of the pole-mounted switch |
| Backup Power Supply | Rated voltage DC24V, single battery capacity ≥7Ah, service life ≥3 years, capable of completing "open-close-open" operation and maintaining operation of the distribution terminal and communication module for at least 4 hours. | Optional 12Ah or other capacity based on user requirements |
| IP Rating | IP65 |