Consult Now

SF₆-Free Gas-Insulated RMU

Product Description

The HXGNA-12 type eco-friendly gas-insulated metal-enclosed AC switchgear is a new-generation power distribution switchgear developed based on the national achievement of the ‘dual-carbon’ goals. Its technical characteristics are utilizing synthesized dry air to replace SF₆ gas as the insulating medium, and employing vacuum switches for the switching of load currents and fault currents. The equipment layout features a three-position switch designed at the upper end of the vacuum switch to convert between conduction, isolation, and grounding functions. The prospective grounding short-circuit current of the line is closed by the vacuum switch within the loop, which can effectively prevent arc pollution to the internal environment of the enclosure during the closing process. The overall dimensions, operating sequence, and ‘five-proofing’ interlocks of the ring main unit fully comply with the regulations of the State Grid typical design schemes.

Product Advantages

SF₆-Free Gas-Insulated RMU

HXGNA-12(紧凑型)
Technical Parameters12KV Circuit Breaker
Rated Voltage kV12
Rated Current A630
Rated Frequency Hz50
Rated Short-Circuit Breaking Current kA20
Phase-to-Phase/Phase-to-Ground kV42
Across the Open Contact kV48
Phase-to-Phase/Phase-to-Ground kV75
Across the Open Contact kV85
Rated Short-Time Withstand Current and Duration kA/s20/4
Rated Peak Withstand Current kA50
Rated Short-Circuit Making Current kA50
Mechanical Life times20000
ItemConfiguration
Power SupplyAC/DC220V + Backup Power
 AC/DC110V + Backup Power
Maximum Monitoring CapacityDigital Input Channels: 105
 AC Analog Input Channels: 56
 DC Analog Input Channels: 2
 Digital Output Channels: 34
 Line/Switch Monitoring Quantity: 16
Communication Interface2 Ethernet Ports, 4 RS232/RS485 Ports
 DLT634.5101, DLT634.5104, MODBUS, DNP3.0
Relay ProtectionPhase-to-Phase Short Circuit and Single-Phase Ground Fault Monitoring
 Three-Stage Three-Phase Overcurrent and Two-Stage Zero-Sequence Overcurrent, Reclosing, Post-Acceleration
Fault RecordingSampling Frequency: 6.4 kHz, 1128 Points/Cycle
 Configurable Number of Cycles, Comtrade 1999 Standard Format
Historical Data StorageEvent Sequence Recording, Remote Control Operation Recording
 Load Curve, Fixed-Point and Extreme Value Recording
 Fault Recording Data
Information SecurityDedicated Security Chip Hardware Encryption
 X.509 Standard Format SM2 Digital Certificate
Performance IndicatorsAnalog Accuracy: Voltage/Current 0.5%, Others 1%
 Remote Signal Resolution: 2 ms
NameEquipment Dimensions
Equipment Dimensions1500*1100*2000
Packaging MethodWood-Steel Edge Box
Packaging Dimensions (mm)1900*1500*2200
Packaging Weight (kg)650
Eco-Friendly Gas-Insulated Ring Main Unit (Example: Three-Compartment Combined Cabinet)20ft Container Capacity L*W*H: 5.89*2.39*2.69m
 40ft Container Capacity L*W*H: 12.03*2.35*2.69m

Success Stories

Product Qualification

Search