The HXGNA-type eco-friendly gas-insulated metal-enclosed AC switchgear is a new-generation power distribution switchgear developed based on the national achievement of the ‘dual-carbon’ goals. Its technical characteristics are utilizing synthesized dry air to replace SF₆ gas as the insulating medium, and employing vacuum switches for the switching of load currents and fault currents. The equipment layout features a three-position switch designed at the upper end of the vacuum switch to convert between conduction, isolation, and grounding functions. The prospective grounding short-circuit current of the line is closed by the vacuum switch within the loop, which can effectively prevent arc pollution to the internal environment of the enclosure during the closing process. The overall dimensions, operating sequence, and ‘five-proofing’ interlocks of the ring main unit fully comply with the regulations of the State Grid typical design schemes.

Product Advantages

Eco-Friendly Gas-Insulated Ring Main Unit

HXGNA-12
Technical Parameters 12KV Circuit Breaker
Rated Voltage kV 12
Rated Current A 630
Rated Frequency Hz 50
Rated Short-Circuit Breaking Current kA 20
Rated Power-Frequency Withstand Voltage for 1 minPhase-to-Ground/Phase-to-Phase kV42
 Across Open Contacts kV48
Rated Lightning Impulse Withstand Voltage PeakPhase-to-Ground/Phase-to-Phase kV75
 Across Open Contacts kV85
Rated Short-Time Withstand Current and Duration kA/s 20/4
Rated Peak Withstand Current kA 50
Rated Short-Circuit Making Current kA 50
Mechanical Life times 20000
ItemConfiguration
Power SupplyAC/DC 220V + Backup Power
 AC/DC 110V + Backup Power
Maximum Monitoring CapacityDigital Input Channels: 105
 AC Analog Input Channels: 56
 DC Analog Input Channels: 2
 Digital Output Channels: 34
 Line/Switch Monitoring Points: 16
Communication Interfaces2 Ethernet Ports, 4 RS232/RS485 Ports
 DL/T 634.5101, DL/T 634.5104, Modbus, DNP3.0
Protection RelayPhase-to-Phase Short Circuit and Single-Phase Ground Fault Monitoring
 Three-Stage Three-Phase Overcurrent and Two-Stage Zero-Sequence Overcurrent, Reclosing, Post-Acceleration
Fault RecordingSampling Frequency: 6.4 kHz, 1128 Points/Cycle
 Configurable Number of Cycles, Comtrade 1999 Standard Format
Historical Data StorageSequence of Events Recording, Remote Control Operation Logs
 Load Profiles, Fixed-Point and Extreme Value Records
 Fault Recording Logs
Information SecurityHardware Encryption with Dedicated Security Chip
 X.509 Standard Format SM2 Digital Certificate
Performance IndicatorsAnalog Accuracy: Voltage/Current 0.5%, Others 1%
 Remote Signal Resolution: 2 ms
NameEco-Friendly Gas-Insulated Ring Main Unit (Example: Three-Compartment Configuration)
Equipment Dimensions1500*1100*2000
Packaging MethodWood-Steel Edge Box
Packaging Dimensions (mm)1900*1500*2200
Packaging Weight (kg)650
20-Foot Container Capacity L*W*H: 5.89*2.39*2.69m3
40-Foot Container Capacity L*W*H: 12.03*2.35*2.69m7