Container-Type Substation
Containerized substation: A complete set of power distribution equipment integrating high and low voltage equipment, transformers, etc., into a movable steel enclosure.
Product Description
Container substation, full name containerized substation, is a complete set of power distribution equipment that integrates high-voltage switchgear, distribution transformers, low-voltage switchgear, energy metering devices, and reactive power compensation devices into a sealed, movable steel structure enclosure. It is suitable for three-phase AC systems with rated voltages of 6-10/0.4kV, 24/0.4kV, and 40.5/0.4kV for power distribution and line use.

Product Advantages
Integrated Design
Transformers, high and low voltage distribution equipment, and intelligent monitoring systems are integrated into a standard container, enabling plug-and-play functionality and significantly reducing on-site installation time.

Modular Structure
Internal equipment adopts modular assembly, supporting customized configurations to meet different capacity and functional requirements (e.g., photovoltaic, energy storage grid connection, wind power).

Energy-Efficient and Eco-Friendly
Environmentally friendly anti-corrosion treatment process with low pollution and low energy consumption during production.

Intelligent O&M
Can be equipped with intelligent substation monitoring and control devices for measurement and protection of electrical equipment inside the substation, enabling real-time monitoring of product operation data.

Container-Type Substation
YB-12/24/40.5kV
YB-12kV
| Item | Parameter |
| Rated Voltage kV | 12 |
| Rated Frequency Hz | 50/60 |
| Rated Capacity kVA | 100~2500 |
| Rated Power Frequency Withstand Voltage kV | HV Cabinet 42 |
| Isolation Gap 48 | |
| Transformer 35 | |
| Rated Lightning Impulse Withstand Voltage kV | HV Cabinet 75 |
| Isolation Gap 85 | |
| Transformer 75 | |
| HV Side Configuration | 12kV Ring Main Unit |
| Transformer Type | Oil-immersed (Dry-type optional) |
| LV Side Configuration | Low Voltage Fixed Switchgear (0.4/0.8kV) |
| Equipment Dimensions (LWH) | 6058*2438*2591 mm |
| Enclosure Specification | 20ft Standard High Cube Container |
YB-24kV
| Item | Parameter |
| Rated Voltage kV | 24 |
| Rated Frequency Hz | 50/60 |
| Rated Capacity kVA | 100~2500 |
| Rated Power Frequency Withstand Voltage kV | Phase-to-Ground and Phase-to-Phase 65 |
| Isolation Gap 79 | |
| Transformer 55 | |
| Rated Lightning Impulse Withstand Voltage kV | HV Cabinet 125 |
| Isolation Gap 145 | |
| Transformer 125 | |
| HV Side Configuration | 24kV Ring Main Unit |
| Transformer Type | Oil-immersed (Dry-type optional) |
| LV Side Configuration | Low Voltage Fixed Switchgear (0.4/0.8kV) |
| Equipment Dimensions (LWH) | 6058*2438*2591 mm |
| Enclosure Specification | 20ft Standard High Cube Container |
YB-40.5kV
| Item | Parameter | |
| Rated Voltage kV | 40.5 | |
| Rated Frequency Hz | 50/60 | |
| Rated Capacity kVA | 1000~6300 | |
| Rated Power Frequency Withstand Voltage kV | HV Cabinet | 95 |
| Isolation Gap | 118 | |
| Transformer | 85 | |
| Rated Lightning Impulse Withstand Voltage kV | HV Cabinet | 185 |
| Isolation Gap | 215 | |
| Transformer | 200 | |
| HV Side Configuration | 40.5kV Ring Main Unit | |
| Transformer Type | Oil-immersed (Dry-type optional) | |
| LV Side Configuration | Low Voltage Fixed Switchgear (0.4/0.8kV) | |
| Equipment Dimensions (LWH) | 6058*2438*2896 mm | |
| Enclosure Specification | 20ft Standard High Cube Container |